3-path ultrasonic flowmeter for heat metering in district heating networks, DN25…2000, up to +180°C, certified to MID MI-004 and OIML R75.

The OPTISONIC 3400 District Heating measures volume flow of heated water and cold in district heating networks, commercial and industrial heat metering, and combined heat and power plants. It is certified to OIML R75 (accuracy classes 2 and 3) and MID MI-004, so it can serve as the flow element of a heat metering system together with a temperature sensor and a heat calculator. The full bore design has no moving parts and no pressure loss, and the direct path configuration is not affected by scaling. Built-in OPTICHECK technology provides sensor and process diagnostics (including NE 107) and a device verification report via HART using the OPTICHECK DTM.

Specifications

Product type
Flowmeter
Product family name
OPTISONIC
Product positioning
For district heating applications
Measurement principle
Ultrasonic
Measured media
Liquids
Process pressure
max. 40 barg/580 psig
Process temperature
-40…+180°C/-40…+356°F
Measuring tube
Austenitic stainless steel (1.4404/316L)
Flange connections
EN (1092-1): DN25…2000 ASME (B 16.5): 1…80"
Certificates/Approvals Custody transfer (CT)
MI-004
Certificates/Approvals Ex
ATEX, IECEx, UKEX
NAMUR compliance
NE 107, NE 21, NE 43, NE 53, NE 80
Analogue outputs
4…20 mA
Discrete outputs
Limit switches, Pulse, Frequency, Status
Digital outputs
FOUNDATION™ Fieldbus, HART®, Profibus-PA, Profibus-DP, Modbus RTU