Skip to content
Krohne Level Transmitter

OPTIFLEX 1100

Guided radar (TDR) level transmitter for continuous level measurement of liquids in storage and buffer tanks, measuring range 0.7…20 m.

The OPTIFLEX 1100 uses Time Domain Reflectometry (TDR) to measure level continuously in buffer, storage, collecting and recycling tanks. It is intended for basic liquid applications in non-hazardous areas and can replace RF capacitance or conductive level transmitters. The converter can be removed under process conditions and rotated 360°, the keypad is reachable without opening the housing cover, and the three available probe types can all be shortened on site.

Specifications

Measuring Principle
Guided radar (TDR)
Measuring Range
0.7…20 m / 2.3...65.5 ft
Process Temperature
-50…+100°C / -58…+212°F
Process Pressure
-1…16 barg / -14.5…232 psig
Probe Types
Three types, all shortenable on site
Application Area
Non-hazardous areas